 | Steam boiler |
|
|
Specification Safe Area Steam Generators
|
|
|
|
|
|
|
Type Steam Generator Burner Maximum Output Normal Working Maximum Working Fuel Consumption Electricity Requirements Power Requirements Water Requirements Container Type Size Safe Working Load Type of Fuel Outlet Connection
Standard Safety Devices
Additional Safety Devices Gas Detection (down at Burner Air Intake)
Certification Steam Generator Lifting Certification
|
Flame Pipe Three Passes Two Stages 4.5 Million BTU/Hr. or 1.13 Million K.Calorie/Hr or 1,319 kW/Hr 5-7 Barg 9 Barg. 21.50 Gallon/Hr. or 140 ltr/Hr at Maximum Load 380/440 V, 3 phase, 50/60 Cycles 7.5 K.Watt One off Fill appr 4,000 ltr 20 Ft container; Boiler Skid Welded to Floor 6.00 x 2.45 x 2.60 mtr high 12,500 kg Light Diesel acc. To DIN 51603 2” Weco Fig 200 Female
Low Water Electrodes Low Water Float Switch Flame Failure by Flame Sensor Maximum Pressure Pressostat Safety Valve set at 9 Barg
Pneumatic Emergency Shut Down Sieger Bias 2 with Sensor Type 780 set at 20% LEL Shut Down
BV or DNV Safe Area Open Deck EN12079
|
|
|
|
|
 |
The working Pressure of the Boiler is maintained by Pressostats, which switch the Boiler on/off around the set level;
|
 |
The Unit contains two feed Water Pumps, which regulate the water level automatically;
|
 |
The Pneumatic ESD is by way of a N.C. Contact in a Pressostat, which in case of emergency (loss of air) will break, which will shut the Boiler down.
|
|
|
|
|
Steam hoses:
|
|
Number & Length Size Maximum Working Pressure Coupling Coding
|
10 off 10 metres 2” or 50 mm 10 Barg. 2” Weco fig.200 BS5342 Type 2A
|
|
|
|
|